Equipment use Type of Equipment User checks Class I Class II
  Formal visual inspection (see note 1) Combined inspection and testing Formal visual inspection (see note 1) Combined inspection and testing
  Not recorded unless a fault is found Recorded Recorded Recorded Recorded
a b c d e f g
Construction sites 110 V equipment S none 1 Month 3 Months 1 Month 3 Months
  IT none 1 Month 3 Months 1 Month 3 Months
  M weekly 1 Month 3 Months 1 Month 3 Months
  P weekly 1 Month 3 Months 1 Month 3 Months
  H weekly 1 Month 3 Months 1 Month 3 Months
Industrial including commercial kitchens S weekly none 12 Months none 12 Months
  IT weekly none 12 Months none 12 Months
  M before use 1 Month 12 Months 3 Months 12 Months
  P before use 1 Month 6 Months 3 Months 6 Months
  H before use 1 Month 6 Months 3 Months 6 Months
Equipment used by the Public S Notes 3, 4 1 Month 12 Months 3 Months 12 Months
  IT Notes 3, 4 1 Month 12 Months 3 Months 12 Months
  M Notes 3, 4 Weekly 6 Months 1 Month 12 Months
  P Notes 3, 4 Weekly 6 Months 1 Month 12 Months
  H Notes 3, 4 Weekly 6 Months 1 Month 12 Months
Schools (see note 4) S weekly none 12 Months 12 Months 48 Months
  IT weekly none 12 Months 12 Months 48 Months
  M weekly 4 Months 12 Months 4 Months 48 Months
  P weekly 4 Months 12 Months 4 Months 48 Months
  H before use 4 Months 12 Months 4 Months 48 Months
Hotels (see note 5) S none 24 Months 48 Months 24 Months none
  IT none 24 Months 48 Months 24 Months none
  M weekly 12 Months 24 Months 24 Months none
  P weekly 12 Months 24 Months 24 Months none
  H before use 6 Months 12 Months 6 Months none
Office and shops S none 24 Months 48 Months 24 Months none
  IT none 24 Months 48 Months 24 Months none
  M weekly 12 Months 24 Months 24 Months none
  P weekly 12 Months 24 Months 24 Months none
  H before use 6 Months 12 Months 6 Months none
Type of equipment references
S Stationary equipment
IT Information technology equipment
M Movable equipment
P Portable equipment
H Hand-held equipment
Notes
1 The formal visual inspection may form part of the combined inspection and tests when they coincide, and is to be recorded
2 Reference to 110 V earthed centre-tapped supply. 230 V portable or hand held equipment is required to be supplied via a 30mA RCD and inspections and tests should be carried out more frequently
3 For some equipment such as children's rides a daily check may be necessary.
4 By supervisor/teacher/member of staff
5 Equipment provided in hotel rooms used by the Public comes under equipment used by the Public (section 3). Equipment in hotels is denoted by items used by the hotel staff